+86-13974939938
EN

Home >Products >Cable and Conductor

Cable and Conductor
  • /upfile/2019/01/17/20190117105319_473.jpg

3.6/6-26/35kV XLPE insulated Cable

This product is applicable to power transmission and distribution system of 35kV and below, and conforms to IEC60502, GB/T 12706

Contact us

  • Product Description
  • INQUIRY
Product Description

Product Characteristics
the highest working temperature of the conductor is 90 ℃
short circuit temperature(5s duration)≤250℃
environment temperature of the cable laying is not less than 0℃
the min. bending radius of cable laying (D is the cable outer diameter):
20 D for 1 core no armoring cable
15 D for 1 core armored cable
15 D for 3 cores no armoring cable
12 D for 3 cores armored cable

Construction Diagram



Type, Name and Usage

 Type

Name

Application Scope

Cu

Al

YJV

YJLV

Copper(Aluminum)  Core XLPE insulated, PVC(PE) sheathed Power Cable

The cable is suitable for laying indoors, in tunnel, cable trench and conduit,  not able to bear external
mechanical forces

YJY

YJLY

YJV22

YJLV22

Copper(Aluminum)  Core XLPE insulated,  Steel Tape Armored , PVC(PE) sheathed Power Cable

The cable is suitable for laying indoors, in tunnel, cable trench and underground, able to bear external
mechanical forces.

YJV23

YJLV23

YJV62

YJLV62

Copper(Aluminum)  Core XLPE insulated, Non-magnetic Stainless Steel Tape Armored , PVC(PE) sheathed  Power Cable

The cable is singlecore cable, laid indoor, in tunnel, cable trench and underground, able to bear external
mechanical forces

YJV63

YJLV63

YJV32

YJLV32

Copper(Aluminum)  Core XLPE insulated, Steel Wire Armored, PVC(PE) sheathed  Power Cable

The cable is suitable for laying in high drop area, can bear external mechanical forces  and moderate pulling force

YJV42

YJLV42

Note: Halogen free, Low smoke and Flame retardant(WDZ), Fire resistant(NH), Flame retardant(ZR)  can be produced,  for high flame retardant cable, ZA-, ZB- shall be added before the normal type.

 

Product Performance
(1) Partial Discharge Test (1.73U0): ≤10PC;
(2) Voltage Withstand Test(3.5U0/5min): no breakdown
(3) Other  technical performances meet IEC60502, GB/T 12706