64/110kV XLPE insulated Power Cable
This product is produced and tested according to IEC 60840, GB/T 11017
Product Description
Product Characteristics
(1) The highest long term operation temperature is 90℃
(2) Short circuit temperature(5s duration)≤250℃
(3) The min.bending radius during the production and installation is 20D.
(4) Corrugated aluminum sheath cable is applicable to light erosion situation and able to bear a certain mechanic force. PVC outersheath is applied to the situation requiring normal fireproofness and insulation, PE outersheath is applied to the direcet burying situation requiring high insulation.
5.The cable should be pre-heated during the laying if the ambient temperature is less than 0℃
Construction Diagram
Product scope
Type |
Rated Voltage |
Core Number |
Cross Section Area |
YJLW02 YJLLWO2 |
64/110 |
1 |
240 300 400 |
Type, name and application
Type |
Name |
Application |
|
Cu |
Al |
|
|
|
|
|
The cable is suitable for laying indoors, in tunnel, cable trench, conduit and high drop area, can bear external mechanical forces and a certain traction, and has reliable longitudinal water blocking function |
|
|
XLPE insulated Corrugated Aluminum sheathed PE Outersheathed Power Cable |
The cable is suitable for laying indoors, in tunnel, cable trench, conduit and high drop area, can bear external mechanical forces and a certain traction, and has reliable longititudal and radial water blocking function |
|
|
XLPE insulated Corrugated Aluminum sheathed PVC Outersheathed Longitudinal Water Blocking Power Cable |
|
|
|
XLPE insulated Corrugated Aluminum sheathed PE Outersheathed Longitudinal Water Blocking Power Cable |
|
ZC-YJLW02 |
ZC-YJLLW02 |
XLPE insulated Corrugated Aluminum sheathed Flame Retardant PVC/PE Outersheathed Power Cable |
Besides the function above, the cable is applied to situation requiring flame retardance and fireproofness |
|
|
XLPE insulated Corrugated Aluminum sheathed Flame Retardant PVC/PE Outersheathed Longitudinal Water Blocking Power Cable |
Product Performance
(1) Partial Discharge Test (1.73U0): ≤10PC;
(2) Voltage Withstand Test(2.5U0/30min): no breakdown
(3) Electrical Test(2.5Kv DC/1min): no breakdown of outersheath
(4) Impulse Vlotage Test(±550kV, 10 times,respectively): no breakdown
(5) Other technical performances meet IEC 60840, GB/11017